- Double-pump system, with self-priming multistage horizontal centrifugal pump with frequency converters (optional) and alternating start-up
- connection possibility of up to two feeder pumps for e.g. 2-cylinder operation
- maximum volume flow up to 25 m³/h
- electronic control with 4-line LCD display
- operating hours counter for each pump
- pressure display of the double pump system
- level indicator of the collecting tank
- manual switch-over to drinking water operation possible
- stagnation circuit individually adjustable
- potential-free fault indicator
- RS 232 interface (ASCI II) for all common building management systems
- everything mounted in a housing made of powder-coated sheet steel
The INTEWA pumping and water control unit PROFI comprises an integrated receiver tank, a double-pump booster system with self-priming multistage horizontal centrifugal pump, an alternating start-up and the electronic control system - all mounted in a housing made of powder-coated sheet steel. The control system constantly monitors the levels in the collection tank and the receiver tank. It includes: 4-line LCD display, operating hours counter for each pump, pressure display of the double pump system, level display of the collecting tank, potential-free fault indicators, RS 232 interface for all common building management systems.
The INTEWA pump and water control units PROFI SC are additionally equipped with frequency converters. The frequency control makes the use of an additional diaphragm compensation tank unnecessary. The SC systems should always be used where long-lasting uniform pressure is required. This is the case, for example, in sprinkler systems with a predetermined throw of the water or cooling of buildings where the water is sprayed in the air conditioning system.
The feeder pump in the collection tank automatically delivers water to the supply tank of the pumping and water station as required. In the event of a water shortage or manual switchover, drinking water is automatically fed into the storage tank as required in accordance with DIN EN 1717. In addition, the solenoid valve is activated regularly to prevent stagnation in the drinking water line. The system is largely self-operating. Only a few manual operations and adjustments are necessary.
Standard version | 16-60 | 10-90 | 16-90 | 30-60 | 30-80 |
---|---|---|---|---|---|
Frequency controlled | n/a | 10-90-SC | 16-90-SC | 30-60-SC | 30-80 SC |
Flow rate max. (m³/h) | 14 | 9 | 14 | 25 | 25 |
Pressure max. (bar) | 5,8 | 9 | 9,2 | 5,9 | 8,4 |
Delivery head max. (m) | 58 | 90 | 92 | 59 | 84 |
Current consumption max. A (supply voltage V) | 2x 6,2 (1x~230) | 2x 3,2 (3x~400) | 2x 3,8 (3x~400) | 2x 4,0 (3x~400) | 2x 6,4 (3x~400) |
Motor power P1 max. (kW) | 2x 1,33 | 2x 1,46 | 2x 2,00 | 2x 2,21 | 2x 3,18 |
Protection class | IP44 | IP44 | IP44 | IP44 | IP44 |
Free outlet | EN1717 | EN1717 | EN1717 | EN1717 | EN1717 |
Width (mm) | 570 | 800 | 800 | 800 | 800 |
Height (mm) | 1325-1335 | 1670-1690 | 1670-1690 | 1670-1690 | 1670-1690 |
Depth (mm) | 630 | 725 | 725 | 725 | 725 |
Weight empty (kg) | 100 | 140 | 150 | 165 | 165 |
Weight max. (kg) | 190 | 310 | 320 | 335 | 335 |
Pressure line connection | 1 ½ " AG | 1 ½ " AG | 1 ½ " AG | 2 " AG | 2 " AG |
Connection feeder pump | 1 ¼ " AG | 1 ¼ " AG | 1 ¼ " AG | 2 " AG | 2 " AG |
Number of feeder pumps | up to 2 | up to 2 | up to 2 | up to 2 | up to 2 |
Connection drinking water | 1 ¼ " AG | 1 ¼ " AG | 1 ¼ " AG | 1 ½ " AG | 1 ½ " AG |
Volume of storage tank (l) | 100 | 200 | 200 | 200 | 200 |
Emergency overflow | DN100 | DN100 | DN100 | DN100 | DN100 |
Level sensor* (m) | 50 | 50 | 50 | 50 | 50 |
Cable level sensor (mm²) | H03 VV-F 2G 0,75 | H03 VV-F 2G 0,75 | H03 VV-F 2G 0,75 | H03 VV-F 2G 0,75 | H03 VV-F 2G 0,75 |
Cable connection feeder pump (mm²) | H03 VV-F 2G 1,5 | H03 VV-F 2G 1,5 | H03 VV-F 2G 1,5 | H03 VV-F 2G 1,5 | H03 VV-F 2G 1,5 |
*no underground cable, factory extendable
ZBP-14 | ZBP-36 | ZBP-46 | |
---|---|---|---|
Diameter [mm] | 160 | 129 | 129 |
Hight [m] | 474 | 563 | 643 |
Suction line | 1 ¼ " IG | 1 ¼ " IG | 1 ¼ " IG |
Pressure line | 1 ¼ " IG | 1 ¼ " IG | 1 ¼ " IG |
Supply line [cable]* [m] | 10 | 20 | 20 |
Flow rate max.[m³/h] | 16 | 16 | 16 |
Pressure max. [bar] | 10 | 20 | 20 |
Plant height max. [m] | 13,5 | 13,5 | 13,5 |
Immersion depth max. [m] | 10 | 20 | 20 |
Protection class | IP68 | IP68 | IP68 |
Rated power [W] | 1100 | 2000 | 2100 |
Supply voltage [V/Hz] | 230 / 50 | 230 / 50 | 230 / 50 |
Weight [kg] | 11 | 19 | 21 |
*no underground cable, factory extendable